TM 5-6350-264-14&P-10NAVELEX EE 181-AA-OMI-110/E121 C-9412T.O. 31S9-2FSS9-1-10condition (by activating a nearbysensor). After expiration of the timedelay period, the Monitor Cabinetshould indicate an alarm condition.(3)Remove cause of alarm, turn modeswitch to TEST/RESET and then toSECURE. At the Monitor Cabinet, goto the Status Monitor Module withalarm lights flashing and move resetswitch to ACK and then to RESET.Monitor Cabinet should indicate asecure condition.(4)Turn mode switch to ACCESS.Monitor Cabinet should indicate anaccess condition.(5)Remove ac power fuse F1 from CUpower supply. AC POWER indicatorlights on Monitor Cabinet shouldchange from on-steady to flashing,and the audible signal device shouldsound.(6)Move reset switch on Status MonitorModule to ACK. Indicator lightsshould go out and audible signaldevice should be silenced.(7)Reinstall ac power fuse F1 in CUpower supply. AC POWER indicatorlights should flash and the audiblesignal device should sound.(8)Move reset switch on Status MonitorModule to ACK. AC POWER indicatorlights should change from flashing toon-steady and the audible signaldevice should be silenced.5-126