T.O. 33B-1-15-87background with the probe pointed to maximize the leak indication). The leakage rate can then beapproximated by the following:Leakage Rate (std cm3/s) = Detection Distance (feet)/2.For example, assume the maximum detection distance is 1 foot.Then:Leakage Rate = 1/2 = 0.5 std cm3/s.5.6.3.2 TestingForInternalLeakswithContactProbe.a. Perform step a. through e. in paragraph 5.6.3 to verify proper operation of the equipment. Use thestandard probe for these steps. If the equipment is not operating properly, it must be replaced orrepaired by the PMEL.b. Connect the contact probe to the instrument. Place the tip of the probe firmly against the test assemblyon a surface close to the suspected location of internal leaks. The tip of the probe should be pressednormal to the surface (see Figure 5-82). Move the probe from spot to spot over the test assembly andnote increases in the meter reading and noise from the earphones or speaker. Noise indications notobserved at similar locations in an assembly known not to be leaking indicate internal leaks in the testassembly. By moving the probe to where the maximum noise and meter reading is obtained, thelocation of the leak can be estimated.Figure 5-82. Correct and Incorrect Application of Leak Testing Contact Probe.
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business