TM 10-5410-228-10
2.2
INVERTER 1A4A13.
1.
OUTPUT VOLTAGE Meter
Monitors inverter AC output voltage (0 to 150 Vac).
2.
I/P IN EXT RANGE Indicator
Lights when inverter is operating in extended input range (18 to 22 Vdc and 29 to 32 Vdc) at
reduced capacity and at higher distortion levels. Inverter shuts down if it falls outside
extended range.
3.
OVER TEMP Indicator
Lights when inverter is in an over temperature condition (thermal shutdown).
4.
OVER LOAD Indicator
Lights when power supplied is greater than 13.3 amps.
5.
O/P OUT OF RANGE Indicator
Lights when inverter output is greater than 122.4 Vac or less than 117.6 Vac. Normal output
is 13.3 amps at 120 Vac.
6.
Monitors inverter output frequency in Hertz (55 to 65 Hz).
7.
DC INPUT (Circuit Breaker/Switch)
Provides input current protection and switches power ON or OFF.
8.
DC INPUT ON Indicator
Lights when DC input switch is in ON position.
2-3