TM 10-6665-297-13&P2-5POWERSUPPLYCONNECTIONS.CD800/830 and CD832 Series Control Modules may utilize the following external power sources:1. 120/240 VAC external power service line.2. Isolated 120/240 VAC plant power unit.3. 12 VDC secondary (standby) power supply.4. Static power converter to accommodate 16 to 35 VDC secondary power supply (compatible with 24 V,32 V battery).5. 12V lead-acid battery and charger.2-5.1POWERCONNECTIONS. External power connections to power terminals for CD800/830 seriesmodels are designated in Table 2-1 and Figures 2-11 through 2-15.Power transformers are factory-wired for 120 VAC operation, as shown in Figure 2-10 diagram A. Transformerwires may be reconnected for 240 VAC operation, if required, as shown in diagram B.NOTE: Model CD800X third wire ground (green) is connected to terminal board terminal labeled "GND:' ModelCD800P third wire ground (green) is connected to AC power terminal strip, terminal "G."Figure 2-10. Transformer Wiring for 120VAC and 240VAC External Power2-5.2DCSECONDARY(STANDBY)POWERSUPPLY. Both AC and DC power may be connectedsimultaneously, so that DC power will be automatically supplied should the main AC power input be interrupted.The standby power supply should not operate from the same generator, converter, or other device that providesthe primary power supply. DC + and - power connections to the control module or module assembly terminalboard are marked 12 V, and + and -, or VDC, +12 an -, depending on the particular model to be installed(CD800P/CD802P: terminals TB-2, 6(+) and 7(-)).2-5.3STATICPOWERCONVERTER. If 24-or-32-volt batteries (or other 16-to-35-23-96177/3/792-13